Abstract

ABSTRACT The outlet velocity field of the pulverized coal burner is one of the important factors affecting its operating characteristics. In this article, cold tests were carried out for a new swirl burner with a pre-combustion chamber, and the influence of the air ratio on the outlet velocity field of the burner was studied. Through the cold single-phase test on the 1:3 model test bench, the burner outlet cold air velocities were obtained. The results shown that the formation of the central recirculation zone was mainly affected by the secondary air, a stable central recirculation zone could not be formed when the velocity of secondary air was too low. When the total air of the burner was fixed, the secondary air increased, the length of the central recirculation zone increased, and the mixing speed between different flows increased. When the ratio of the mass flow of the secondary air to tertiary air increased from 26:74 to 85:15, the reflux rate increases 5.5 times, which helped to keep the combustion stable.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.