Abstract
This paper examined the extent of the dependence of the interrupting capability on the shape of the contact system in a molded case circuit breaker (MCCB). Thus, a simple analysis method was suggested for estimating the interrupting capability and used to investigate the magnetic flux density distribution in a contact system caused by a short-circuit current. However, the MCCB produced by a joint-research company turned out to have the poor interrupting capability and a low magnetic flux density distribution for driving arc plasma between two contacts in the contact system. To build up additional interrupting capability without making many changes, a new arc runner was devised to prevent arc plasma from returning to its original position in the contact system. The arc voltage characteristics were tested with a simplified synthetic testing facility using an LC resonant circuit. The result showed that the new MCCB had a much higher arc voltage than the existing MCCB. This implies that investigating the arc voltage is fairly comparable to predicting the arc plasma extinction and the interrupting capability.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.