Abstract

In this paper, we present an investigation into the influence of the load power factor of secondary winding on the metrological performance of inductive CTs with frequencies from 50 Hz to 5 kHz of the harmonic of a transformed distorted current. The results clearly indicated that the inductive load caused a deterioration in the transformation accuracy of the inductive CT. To ensure the most advantageous conditions of their operation, a resistive load should be used. The inductive CTs for the frequencies of the transformed harmonic of a distorted primary current from 50 Hz to 5 kHz may ensure the accuracy class designated for the transformation of the sinusoidal current of a frequency of 50 Hz with the same limiting values of errors. Moreover, an analysis of the generated low-order harmonics by a 300 A/5 A CT determined for the power factor of 0.8 inductive and 1.0 of the secondary winding was investigated. These results for the transformed distorted currents of 3rd, 5th and 7th higher harmonics were evaluated for a rated load and 25% of this value.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call