The objective of this study is to determine the potential energy savings and thermal comfort benefits of exposing concrete in the ceiling to the indoor air as an alternative to suspended ceiling. The performances were assessed through monitoring of room air and surface temperatures in an office building in operation, and simulation of different scenarios with a calibrated building simulation model. In this study, it is shown that ESP-r is capable of simulating an advanced controlled office building in operation with good agreement with the measurements. The results presented in this paper indicate that exposed concrete in the ceiling both reduces the number of hours with excessive temperatures considerably and create a better and more stable thermal environment during the working day. Also, exposed concrete increases the achievements of utilizing night free cooling significantly. However, by removing the suspended ceiling, only minor annual heating energy savings are achieved.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.