Abstract
After COVID-19, two ventilation approaches have been adopted for infection control. The first is the EN 16798-1 ventilation standard recommended by international organizations. The second is ventilation design, determined according to the risk of infection. This study investigated the effects of various post-COVID-19 ventilation scenarios on the probability of COVID-19 infection, the number of cases, and ventilation rates in four separate university classrooms. Ventilation rates based on infection risk and infection risk were determined by the Wells-Riley mathematical model calibrated to the SARS-CoV-2 virus. The findings showed that the EN 16798-1 ventilation standard may be inadequate in terms of infection risk in classrooms. It showed that ventilation rates determined based on infection risk may not be met by existing HVAC system capacities, even in LEED-certified schools. In possible future pandemics, current ventilation standards and air conditioning system designs in schools should be reviewed in order to control the outbreak.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.