Abstract
The aim of the work is to determine the permissible load factors of step-down transformers when powering various types of greenhouse irradiators. All examined irradiators have nonlinear volt-ampere characteristic and generate upper current harmonics. The object of research are greenhouse illuminators with high pressure sodium lamps, induction and light-emitting diodes greenhouse illuminators (LED) with active and passive power factor. The permissible load factors of transformers are calculated using obtained data: for high-pressure sodium lamp light is 0.95 max; for LED lamps with active power factor corrector – 0.76 max; for LED lamps with passive power factor correction – 0.59 max; for electrodeless lamp light – 0.98 max. To reduce current harmonics in systems with LED lamps and to increase the load factor of transformers, it is necessary to apply special devices – active or passive harmonic filters. For greenhouse irradiators with sodium lamps and induction irradiators, the use of harmonic filters is not required.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Earth and Environmental Science
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.