Abstract

This research was conducted to determine the effect of changing the type of lamp, the addition of power, and the number of lighting points to the strength of the lighting in the Classroom and Reading Room of the Postgraduate Program at the Bung Hatta Building, Jakarta State University. This research was conducted because the room has strong lighting that is too large during the day and too low at night. This research uses a quantitative approach with a descriptive engineering method through three stages of engineering namely manual measurement using Luxmeter, manual calculations based on SNI standards, and simulations. The results showed that when the treatment has not been done, the average value of the measured illumination and based on the simulation results in the reading room (6th floor) and lecture room (7th and 8th floor) do not meet SNI 03-6197: 2011 Standards. Through changing the type of lamp, the addition of power, and the number of points 15 rooms meet the standards with an average optimization presentation of 20% to 88%.