Abstract

SummaryThe paper aims to explain the differences found in the heat release rate measurements in a large sample of standard fire tests (EN 1363‐1). A total of 379 tests of vertical assemblies was investigated, all performed in furnace SPARK of the ITB Fire Testing Laboratory, in 2015‐2018. The assemblies were subdivided into two groups—wall assemblies and fire‐rated doors. These assemblies were also compared with the results of the test of a wall built with aerated autoclaved concrete blocks that was considered as the benchmark test. It was observed that walls built with highly insulated sandwich panels require less heat to maintain standard thermal exposure conditions (20%‐30% less) than their counterparts built from gypsum plasterboard or aluminium and fire‐rated glass. In case of doors, it was observed that combustible samples required significantly less heat than the benchmark case (40%‐70% less), which indicates that the combustion of the sample inside of the furnace was an additional, significant source of heat release, that may skew the qualitative assessment of their performance in fire. A more in‐depth discussion of the results is provided, with some ideas on the direction of further developments in fire testing.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.