Abstract

The stability margin of a conduction-cooled LTS pulse coil with stored energy of 1 MJ, which is used for UPS-SMES as protection from momentary voltage drops, is estimated from thermal analyses using the two-dimensional finite elementary method. How much the 1 MJ coil is able to be downsized is discussed. The winding conductor of this coil is a NbTi/Cu Rutherford cable, which is extruded with aluminum. Dyneema FRP and Litz wires are used as the spacers of this coil. In the design of this 1 MJ coil, the effects of spacers were neglected. In order to estimate the stability margin, thermal analyses was carried out by taking into account the thermal effects of spacers, for the coil during overload operation. And it was checked whether the maximum temperature The results showed that the 1 MJ coil has a large stability margin of 8 times the rated ac loss. In addition, new coils with a stability margin of about two times were designed. Possibilities for reducing the size and the cost of a 1 MJ LTS pulse coil are also shown.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.