The design and testing of high-voltage shunt reactors is discussed. The advantages of a gapped-core construction employing radial laminated limb sections with a relatively small number of air gaps, resulting in a simple mechanical construction, are described. A comparison is made between testing methods for transformers and reactors, special attention being paid to test power, loss measurement, measuring accuracy, and special tests. A bridge method for loss measurements is described. Among the various dielectric tests discussed, particular mention is made of the induced voltage test and its unrealistic representation of actual service conditions. It is suggested that this test be replaced by one utilizing a lightly damped oscillation produced by an impulse generator. The need for vibration measurements as a check on mechanical behavior is stressed.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.