Abstract

This research evaluates one method of increasing the performance of an air sourced heat pump to extend its operating range and eliminate the need for a backup heating system. A study was conducted using the Engineering Equation Solver software package to identify the performance improvements that are attainable with variations of a two stage heat pump cycle. An experimental apparatus was constructed to compare the performance of the best performing variation - a two stage economized cycle - to that of a traditional single stage heat pump. The two stage economized heat pump had a measured coefficient of performance of 1.45 when it was operated at an outdoor temperature of -31C making it an energy efficient option for most Canadian climates. In addition, the heating capacity of the system was increased by a factor of 2.5 when compared to the single stage system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.