Abstract
We investigate and address the performance limitations of the ATLAS silicon tracker fluorocarbon evaporative cooling system operation in the cooling circuits of the barrel silicon microstrip (SCT) sub-detector. In these circuits the minimum achievable evaporation temperatures with C3F8 were higher than the original specification, and were thought to allow an insufficient safety margin against thermal runaway in detector modules subject to a radiation dose initially foreseen for 10 years operation at LHC.We have investigated the cooling capabilities of blends of C3F8 with molar admixtures of up to 25% C2F6, since the addition of the more volatile C2F6 component was expected to allow a lower evaporation temperature for the same evaporation pressure.A custom built recirculator allowed the in-situ preparation of C2F6/C3F8 blends. These were circulated through a representative mechanical and thermal setup reproducing an as-installed ATLAS SCT barrel tracker cooling circuit. Blend molar compositions were verified to a precision of 3.10−3 in a custom ultrasonic instrument.Thermal measurements in a range of C2F6/C3F8 blends were compared with measurements in pure C3F8. These indicated that a blend with 25% C2F6 would allow a reduction in evaporation temperature of around 9̂C to below -15̂C, even at the highest module power dissipations envisioned after 10 years operation at LHC. Such a reduction would allow more than a factor two in safety margin against temperature dependant leakage power induced thermal runaway.Furthermore, a blend containing up to 25% C2F6 could be circulated without changes to the on-detector elements of the existing ATLAS inner detector evaporative cooling system.
Highlights
1.2 The ATLAS inner detector C3F8 evaporative cooling system The ATLAS Inner Detector (ID) contains a multi-layer silicon tracker
We have constructed a custom thermodynamic recirculator that has been used for investigations of the cooling capabilities of C2F6/C3F8 blends with molar admixtures of up to 25% C2F6
The test structure incorporated an exhaust heat exchanger, an electric heater, backpressure regulator and intervening tubing identical to those used in the installed Semi-Conductor Tracker (SCT) system
Summary
It can be seen that a reduction in operating temperature of at least 8.5◦C is possible for all power levels in a blend containing 25% C2F6
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.