Abstract
Hybrid-HVDC is a new topology which is consisted of Line-Commutated-Converter (LCC) and Voltage Source Converter (VSC). It combines the advantages of LCC and VSC. Two topologies of Hybrid-HVDC were studied and found their application prospects. The structure which the rectifier station using VSC is suitable for connecting offshore wind farms, while the inverter station using VSC is suitable for supplying the passive network. The control strategy for Hybrid-HVDC is designed which introduce the voltage margin control and voltage dependent current order limiter control. The simulation of the Hybrid-HVDC which consists of a two level VSC converter and a bipolar12-pulsation converter is done in PSCAD. The designed structure can be run in monopole when DC fault occurs. The steady state characteristics and the fault conditions were studied. Furthermore, the optimal control strategy for this hybrid structure is selected.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.