Abstract
The very fast transient overvoltage (VFTO) is changed when stepped controllable shunt reactor (SCSR) is installed in substation, this paper simulates and analyzes the closing sequence of the disconnector (DS) and voltage transformer (PT) installation location’s influence on VFTO with Dommel transmission line, and establishes the VFTO suppression equivalent impedance model in frequency domain, and analyzes the effect of various measures to suppress VFTO time-frequency amplitude. The results show that the VFTO dominant frequency and the corresponding amplitude can be reduced by reasonable choice of DS closing sequence and PT installation site. Compared to the closing resistor, ferrite has advantages in suppressing VFTO. The peak of VFTO increases first then decreases with the increase of the length of the ferrite.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: IOP Conference Series: Materials Science and Engineering
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.