Abstract
This paper deals with the results of tests made on the divided and confluent flow at the branch part of the special type tee fitting for a rectangular air duct. As the results of experiments, the empirical formurae for the coefficient of resistance in the confined two streams in the rectangular air duct have been obtained.(1) Loss in the divided flow at the branch part.upside type fitting P=0.9Hm+1/3Hb flank type fitting P=1.5Hm-0.79√Hb·Hm+0.11 Hb(2) Loss in the confluent flow at the branch part.upside type fitting P=-0.6Hm+1.4Hb flank type fitting P=-0.4Hm+1.0HbWhereP=pressure loss, mm WGHm=velocity head in the main duct, mm WGHb=velocity head in the branch duct, mm WGb=breadth of the main duct, mm
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.