Abstract

The time constants of the D.C. component of asymmetrical fault current are trend to increase. It is said that interruption capability of gas circuit breaker degrades at asymmetrical current interruption.This paper shows the investigation of the interruption capability of 550kV one-break SF6 gas circuit breaker at asymmetrical current interruption. Interrupting tests of asymmetrical current with time constant 100ms, 150ms were carried out in high power laboratory. At the interrupting tests, arcing time was changed due to the time constant of the D.C. component. From the interrupting test results, arc energy was calculated. Degradation of the interrupting capability at asymmetrical current interruption was investigated by using measured arc energy.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.