Abstract
The grounding capacitive current is one of the most important parameters of ungrounded neutral system. Usually this parameter is obtained with the method of additional capacitor or metal grounding. However, the former is complicated and the additional capacitor has negative effects on measurement results, and the later is dangerous when used in testing. In view of that, the paper proposes a new method to calculate grounding capacitance current based on the data of single-phase-grounding faults in power system with indirectly earthed neutral. This method reduces the error by using the least-square method .The ATP simulation results show that this method is accurate basically.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.