Abstract

Oil-immersed insulating material has an anisotropic and nonlinear conductivity, so the direct current (dc) electric field calculation should take these factors into consideration. In this paper, a new calculating method based on ANSYS secondary development technology is proposed. Then, the nonlinear and anisotropic dc electric field is calculated, considering electrical stress and temperature impact on conductivity. The results show that the electric field distribution calculation is very different if considering or not considering these factors. Therefore, the converter transformer insulation design should be calculate as anisotropic and nonlinear field.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.