Abstract

Statistics of wound infections demonstrate the linear dependence between postoperative wound infection and the quantity of bacteria in the air of operating theatres. In the most extensive examination series we have made as yet with a special work group of DGOT the quantity of bacteria in the air of non air-conditioned operating theatres and such fitted out with different aircleaning systems was determined. Non air-conditioned operating theatres proved so extremely infected that the risk of wound infection cannot be borne any more in the future. Also air-conditioned systems according to DIN 1946/4 with an average of 190 bacteria/m3 are not sufficiently secure for bone and joint surgery. In Switzerland for such operations a value of 10/m3 at the most is admissible. Such equivalents have been attained only with LAF until today. After extensive air tests the so-called "Keimstop"-system by Meierhans and Weber is to be considered the sole system suitable to supplement air conditioning DIN 1946/4. This combination yields the same effect as the expensive LAF systems.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.