Abstract

This experimental study is carried out to investigate reliability and effectiveness of a new method of using photo-coupler for detecting frost formation in an air source heat pump, and further to determine the most efficient initiation point of the defrost cycle. This new method of using photo-coupler as a frost sensing device is evaluated by comparing its performance with conventional time control defrost system in which defrost cycle is set to start at predetermined interval, e.g. about at every 1–1.5 h. Results indicate that overall heating capacity of photo-coupler detection method (case IV) is 5.5% higher than that of time control method. It is also shown that for maximum efficiency the defrost cycle must be initiated before the frost build-up area exceeds 45% of total front surface of the outdoor coil.