Abstract

The paper presents an algorithm that is used to detect the loss of excitation (LOE) of synchronous generators. The algorithm is implemented on the principle of a digital phase comparison in the time domain. The digital phase comparator calculates the integral of the instantaneous power of the input signals. The algorithm uses the currents and corresponding line voltages obtained by the measurements available at the terminal of the generator as their input signals. The input signals are phase-compared on the basis of the value of loss of excitation index after which the LOE is detected. The software package MATLAB/Simulink includes the test power system along with the synchronous generator which simulates the phenomenon of LOE. The algorithm has been tested for total and partial LOE and stability power swing for different operating modes of a synchronous generator. The test results show good properties of the proposed algorithm.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.