Abstract

The equivalent voltage source method is recommended in IEC 60909 for short-circuit current calculation, and the accuracy is verified by 400 kV and below voltage level power grids. There are 500 kV, 750 kV or 1000 kV power grids in some countries where IEC standards are applied, but there is no relevant research to verify the accuracy of the calculation method. In this paper, verification methods for IEC 60909 calculation accuracy for the three voltage level power grids are adopted. Calculation examples based on the operation and equipment parameters of the 500 kV, 750 kV and 1000 kV power grids are established. The results show that IEC 60909 short-circuit current calculation method is conservative, and the calculation accuracy meets the requirements. The research expands the application scope of this standard to all AC power grids, which is conducive to the engineering application of IEC 60909.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.