Abstract

The Superconducting Fault Current Limiters are very attractive devices for the electrical power network. The performance comparison of inductive SFCL with three different secondary windings are presented in this paper. As secondary windings we used Bi-2223 tube, HTS tape and HTS tape parallel rings. We proved that the limiting capabilities of the SFCL with different windings are comparable, and the windings made of HTS tape are less expensive and more mechanically stable then HTS tubes. We proposed two method of implementation of shorted secondary winding. The experimental results show that HTS tube can be successfully substitute by cheaper shorted winding made of HTS tape.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.