Abstract

The Ultera/ORNL team have built and tested 3-m and 5-m triaxial cables rated at 3 and 1.3 kA-rms, respectively. The three concentric superconducting phases are made of BSCCO-2223 HTS tapes, separated by layers of cold-dielectric tapes. A copper braid is added as the grounding shield on the outside of the three active phases. Tests of these cables were performed at temperatures ranging from 70 to 84 K. AC loss data reconfirmed the previous result on a 1.5-m prototype cable that the total 3-phase ac loss is about the sum of the calculated ac losses of the three concentric phases. These and other test results of the 1.3 and 3 kA cables will be used to construct a second 5-m triaxial cable rated at 3 kA-rms, 15 kV. Preliminary test results supporting this new cable and the associated termination are summarized.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.