Abstract

The advantages of high-speed reclosing of transmission lines in 20 cycles or less are well established for voltages up to 138 kv. Up to this date little information is available however on reclosing 230 kv lines in 20 cycles or less, because breakers have not been available for such fast operation. This paper describes a 230-kv oil circuit breaker which is suitable for three-pole or single-pole reclosing with a reclosing time of less than 20 cycles. The performance of the breaker is established by field tests for high-speed-reclosing operation as well as for interruption of charging currents.