Abstract
The paper deals with the experimental testing of the efficiency of the operation of an air/water heat pump in connection with three radiant systems in heating mode in an office building, which is part of the central laboratories of the Slovak university of Technology in Bratislava. The testing was aimed at verifying the manufacturer's theoretical claims about efficiency of the heat pump based on the COP and SCOP values according to EN 14511-1:2022 and EN 14825:2022. The testing period was from 7 Jan. 2024 until 15 Jan. 2024. The aim of the testing measurements was to evaluate the calculated value of SPF efficiency for individual days and for the testing period. During the measuring period, the wall radiant system consumed 188 kWh, the ceiling system 216 kWh, and the floor radiant system 196 kWh. The heat pump consumed 227 kWh of electricity. The calculated SPF value was 2.64.
Published Version
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.