Abstract

The IEC Standard 61482–1 describes procedures for measuring the thermal performance of fabrics and garments intended for use in clothing for workers exposed to electric arcs. This paper demonstrates that the tests in this standard fail to produce controlled laboratory conditions. The dominant magnetic and thermal buoyancy forces have been minimised leaving two undefined and uncontrolled forces to randomly dominate arc motion, plasma flow and thermal stress. The tests also produce hazards significantly different to those facing victims in real situations. The velocity of the plasma impinging on a victim is incorrect. The color of the radiation is incorrect. The molten metal droplets impinging on the victim are incorrect. The tests only consider clothing stretched over a surface whereas loose and un-backed cloth suffers considerably more stress. In order to emulate real arcing faults, it will be necessary to use parallel copper and aluminium electrodes. In addition for high voltage personnel a “pop-out” test needs to be developed because a fault current that starts by entering and exiting the body becomes an arc inside the clothing.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call