Abstract

The tests described in this paper are part of an Electric Power Research Institute (EPRI) program (Research Project 2172-2) to provide a test-verified analytical method of estimating capacities of concrete reactor containment buildings under internal overpressurization from postulated degraded core accidents. Experimental study in Phase 2 of the investigation, on which this paper is based, includes tests of five large-scale specimens with steel liner plates representing structural elements of prestressed concrete containment buildings. Four square wall element specimens and one specimen representing the wall/basemat junction region were tested. This experimental work indicates that under internal overpressurization or other accident conditions, highly localized strains in the steel liner plate can result in liner tearing and subsequent containment leakage. These results support the theory of leak before break where liner tearing occurs in a controlled manner and leakage and depressurization occur rather than global failure.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.