Abstract

Methods for minimizing the error in an estimate of the voltage at a given probability of flashover (e. g., 3 sigma withstand) are presented. The variance in the estimate of a voltage is minimized with respect to the applied voltage and the number of applications of that voltage. It is shown that testing at approximately 5-percent and 95-percent probability of flashover yields maximum information about such quantities as 2 sigma and 3 sigma withstand voltages, and standard deviation.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.