Abstract

We present results from commissioning testing of a 1 MVA three-phase transformer demonstration project. The three-phase transformer utilizes a 15 strand Roebel cable for the low voltage windings and 4 mm wide conductor for the high voltage windings. Both windings use ReBCO conductor and the iron core is external to the cryogenic region. The target operating temperature is 70 K. Key design features and operational performance measures of the advanced sub-cooled liquid nitrogen circulation system are described. The overall thermal budget is presented along with ac loss measurements for the windings and electrical test results of the complete transformer. There remain some unresolved issues with the stability of the cryogenic cooling system when operated sub-cooled, and with the high voltage withstand performance of the HV bushings. These issues are described and discussed. The utility of HTS Roebel cable as a convenient means of producing a compact, high current winding with low ac loss characteristics has been successfully demonstrated.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.