Abstract
Based on test analysis and simulation calculation of temperature field for dry-type air-core reactor, the temperature rise rule of internal axial dimension and enveloping internal conductor were analyzed. The highest temperature rise point in the envelope is located about 1/4 of the packet seal. The temperature rise difference between the inner wires is small, and the temperature rise difference within the envelope is less than 1 °C. The radial distribution of temperature along the insulating impregnated glass fiber has a great gradient. The temperature in the middle of the airway is near room temperature, and the temperature rise is about 5K, and the internal temperature of the airway has a larger gradient. For airway width design, the influence of the change of the airway width of the temperature rise distribution should be considered.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have