Abstract

Foundation piles used as heat exchangers as part of a ground energy system have the potential to reduce energy use and carbon dioxide emissions from new buildings. However, current design approaches for pile heat exchangers are based on methods developed for boreholes which have a different geometry, with a much larger aspect (length to diameter) ratio. Current methods also neglect the transient behaviour of the pile concrete, instead assuming a steady state resistance for design purposes. As piles have a much larger volume of concrete than boreholes, this neglects the significant potential for heat storage within the pile. To overcome these shortcomings this paper presents new pile temperature response functions (G-functions) which are designed to reflect typical geometries of pile heat exchangers and include the transient response of the pile concrete. Owing to the larger number of pile sizes and pipe configurations which are possible with pile heat exchangers it is not feasible to developed a single unified G-function and instead upper and lower bound solutions are provided for different aspects ratios.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.