Abstract

A technique is proposed in this letter to study the voltage collapse situation in a radial distribution network. The radial distribution network has been reduced to a single line equivalent circuit and then represented through a /spl pi/ network. A stability index is developed that indicates the severity of the loading situation of the system. The index can have a maximum value of one (1.00) when the system is at the point of collapse and a minimum value of zero (0) when there is no load in the system. Voltage collapse can be assessed based on the value of the developed index. If the system yields a value exceeding its maximum limit of stability index (1.00) it indicates a voltage collapse situation. The proposed technique is tested on a practical system of a 12-bus radial system (main feeders only) and on a 27-bus radial distribution system with laterals. The results obtained are encouraging and indicate that the technique has the potential to be used as a tool for system monitoring and future load planning.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.