Abstract
In recent years, there was an increase of ancillary service loads, such as signaling systems, inspection robots, surveillance cameras, and other monitoring devices distributed along high-voltage transmission lines which require low-power dc voltage supplies. This paper investigates the use of the induced voltage in the shield wires of an overhead 525 kV transmission line as a primary power source. Since phase current variations throughout the day affect the induced voltage in the overhead ground wire, a step-down dc-dc converter is used after rectification of the ac voltage to provide a regulated dc output voltage. The initial encouraging results obtained indicate that this form of power supply can be a feasible and cost-effective alternative for feeding small ancillary service loads. The simulation results are validated by field measurements as well as the installation of a 200 W voltage stabilization system prototype.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.