Abstract

To conduct the mainly active load current test duty according to IEC 62271-103, a directly powered test circuit and therefore a medium voltage connection or a power generator is needed. A newly developed synthetic test circuit allows to replicate the current as well as the full transient recovery voltage (TRV) and the power frequent recovery voltage (RV) of the direct test circuit up to its crest value. It is dimensioned for voltage classes up to 52 kV and can be adapted to test currents between 630 A and 1250 A. The test circuit allows a detailed investigation of load break switches without costly high power sources and loads. Many parameters, like current and voltage steepness at current zero, as well as different parameters defining the TRV steepness can be varied individually.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.