Abstract
An online post-fault transient stability assessment method is proposed in this study using synchrophasor or PMU measurements. Initially, a post-fault multimachine system is converted into a suitable one machine infinite bus (OMIB) system using the single machine equivalent (SIME) method. Thus, the - trajectory obtained through the OMIB system enabled a normalized transient stability index to be calculated offline. By using synchrophasor measurements before and during the fault as inputs, the regression model can be trained offline to predict the normalized stability margins. Following a fault, the synchrophasor measurements are used as input to this trained model for online stability margin prediction. If the predicted margin is negative, then the post-fault power system is indicated to be unstable. Alternatively, positive values for the predicted margin identify the system as stable. The proposed assessment method is verified using the New England (NE) 39 bus test system. The results obtained are then compared with offline simulations.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
More From: ECTI Transactions on Electrical Engineering, Electronics, and Communications
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.