Abstract

This paper unfolds the issue of synchronizing stability in doubly fed induction generator (DFIG)-based wind turbines when connected to weak AC grid. In weak AC grid, the turbine's terminal voltage vector (both amplitude and phase angle) is significantly influenced by the vectors of the grid voltage and DFIG's internal potential that is contributed by both stator and grid-side converter (GSC). Currently, most developed DFIGs synchronize with grid by phase locked loop (PLL) which generates the phase angle by detecting terminal voltage. The complex dynamics of terminal voltage may deteriorate the performance of PLL and destabilize it under large-signal disturbance, which may lead to synchronizing instability of the DFIG system. In this paper, a DFIG-based wind turbine connected to infinite bus via high grid impedance is studied. The structure of PLL in weak AC grid is given and the equal-area method is adopted to investigate the large-signal stability of it conceptually. Simulation results verify the loss of synchronizing stability of DFIG.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.