Abstract

Using a 300kV puffer-type gas circuit breaker (GCB) combined with a 275kV-150MVA shunt reactor or a test air core reactor at a laboratory, the authors measured surges during reactor current interruption. Such surges as chopping current, single reignition, and multireignition surges were observed. To explain the mechanisms of these surges, the authors measured precisely high-frequency reignition currents with the help of an optical device. Multireignition surges seem unlikely to occur in actual fields.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.