Abstract

The hybrid AC/DC microgrid gains a great attention in recent years as it can improve the energy efficiency and ensure the reliability of the system. This paper makes an investigation on the operation mode switching performance of an AC/DC combined hybrid microgrid based on a real system at Griffith University, Queensland, Australia. An improved virtual synchronous generator (VSG) control strategy is developed to optimize the switching performance from the grid-tied mode to the islanding mode. The basic VSG principle is described and the improved VSG model is introduced. Based on the improved model, a pre-synchronization method is proposed. Comparison of the microgrid performance between conventional droop control and the improved VSG control is carried out by simulation on Matlab/SIMULINK environment. Simulation results show the advantage of VSG control strategy and the validity of the pre-synchronization method.

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call