Abstract
Investigation of epidemic outbreaks of Legionnaires disease by Center for Disease Control personnel has resulted in the isolation of Legionella pneumophila from water in the air-conditioning cooling towers or evaporative condensers at the site of the outbreak. It is suspected that improperly maintained open, recirculating water systems may play a role in the growth and dissemination of this pathogen. The objective of this study was to determine the antimicrobial activity of three chemically different, commercially available, cooling tower microbicides against L. pneumophila. Using two in vitro test systems, a combination of N-alkyl dimethyl benzyl ammonium chloride and bis (tri-n-butyltin) oxide was found to kill L. pneumophila at a concentration 25 times less than the minimum recommended use concentration, whereas N-alkyl 1,3-propanediamine and methylene bis (thiocyanate) were active at concentrations equal to or greater than the concentrations recommended for use by the manufacturer.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.