Abstract

Special instrumentation was developed for monitoring the magnitude and frequency of occurrence of surge voltages in residential and industrial circuits. Over a period of 2 years, more than 400 locations in 20 cities were surveyed. Monitoring was accomplished by automatic recording cathode-ray oscilloscopes and simple surge counters. In residential circuits, two significant sources of surge voltages were identified: load switching within the house, and external surges, most likely associated with lightning, coming through the service drop. In industrial circuits, the levels of surges are lower than in residential circuits. However, switching surges on the load side of the switch can be severe. Internally generated surges as high as 2500 volts were recorded during this test program, and surges due to lightning reaching 5600 volts have been recorded on a 120-volt overhead distribution line.