Abstract

AbstractThis paper proposes an extended method of zero‐voltage switching (ZVS) range for a dual active bridge (DAB) matrix converter with a discontinuous current mode (DCM). In the traditional DAB converter, ZVS cannot be achieved at a light load condition. The duty ratio calculation to achieve power factor correction and ZVS is explained using a circulating current. From the experimental results using a 5‐kW prototype, the ZVS operation with zero transmission power is achieved by increasing the circulating current. In addition, the grid current distortion is lower than 5.0% at the rated power regardless of the DC voltage variation of plus or minus 20%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.