Abstract

Surface spark-over voltages on solid insulators in boiling and sub-cooled liquid nitrogen are studied under ac, dc and impulse voltage. The insulator structure used is a model of a power cable end. In the structure, static capacitance is formed between outer surface and inner conductor of the insulator. The spark-over voltages for several insulators were measured at gap length 60 mm or less under each voltage waveform. The spark-over voltages increase slightly with increasing gap length in boiling and sub-cooled liquid. In range of shorter gap length spark-over voltages in sub-cooled liquid are higher than those in boiling liquid nitrogen. The differences between spark-over voltages in both liquids are caused by bubbles generated due to discharge at low voltage. The spark-over voltage for the insulator with the larger static capacitance is lower than that for one with the small capacitance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.