Abstract

Corona discharge is recognized as one of the mechanisms that can influence the surface hydrophobicity of Silicone Rubber (SR) because of the chemical changes that occur on its surface. In this study SR samples were exposed to positive and negative DC corona for 25 and 50 hours using a needle-plane electrode system. Hydrophobicity changes were monitored using a sessile drop contact angle measurement facility. The physical changes on the surface were studied using Scanning Electron Microscopy (SEM) and surface roughness measurements. The effect of positive dc corona was found to be different from that of negative dc corona. Significant surface degradation and loss of hydrophobicity was found in the case of negative dc corona exposed samples. Significant improvement in the above mentioned properties were obtained by adding small quantities of nSIL into the SR matrix.