Abstract

Surface charge accumulation on spacer is an important factor to cause surface flashover. An experimental set-up is established to measure surface potential over a truncated cone-type spacer under DC voltage in SF 6 gas at atmospheric pressure using a Kelvin vibrating electrostatic probe. The surface charge density is calibrated based on multipoint measurement technique, which takes the influence of electrostatic probe into account. The experimental results show that surface charge distribution patterns can be divided into three classes including centrosymmetric distribution, spot-like distribution, and cloud-like distribution. The symmetrically distributed charges are injected by electrode, which migrate along spacer surface through the surface conductivity. While the charges showing spot-like and cloud-like distribution are generated by the ionisation of SF 6 due to local electrical field concentrated. Besides, the hetero-charges are more easily to be saturated with different charging durations and the polarity of the net charge is the same as that of applied voltage.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.