Abstract

Surface analysis of 400 kV silicone rubber composite insulators is presented. These insulators have experienced 15 years of service on a coastal 400 kV transmission line. Inspection of the insulators shows low levels of degradation through cracking and oxidation of title surface. This has been quantified by microscopy, energy dispersive X- ray analysis (EDX), Fourier transform infrared spectroscopy (FTIR) and Raman spectroscopy. The analysis shows non-uniform ageing over each shed and ageing on the south side more advanced than on the north side. It is believed that non-uniform ageing was due to environmental factors including natural UV radiation and prevailing wind direction, and the resultant pattern of growth of organic species. EDX and FTIR were found to be the most useful and effective tools for analysis of these polymeric insulators.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.