Abstract
Water mist suppression tests for glass-reinforced polyester (GRP) panels were conducted in ISO 9705 Room. GRP panels covered part of the room and a wood crib fire was used as fire source to ignite GRP fire. A four-nozzle water mist suppression equipment was used inside test room on the time of flashover. Heat release rate of the combustion inside the room, room temperature, surface temperature of GRP panels, total heat flux to wall, ceiling and floor in specific positions were measured. Gas concentration of O2, CO, and CO2 was also measured in the corner of the room at two different levels. A thermal image video was used to record the suppression procedure inside room. Test results show that the water mist system is efficient in suppressing the flashover of GRP fire and cooling the room within short time.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.