Abstract

This paper describes a control scheme to mitigate inter-area oscillations through active damping. The control system uses real-time phasor measurement unit (PMU) feedback to construct a commanded power signal to modulate the flow of real power over the Pacific DC Intertie (PDCI) located in the western North American Power System (wNAPS). A hardware prototype was constructed to implement the control scheme. To ensure safe and reliable performance, the project integrates a supervisory system to ensure the controller is operating as expected at all times. A suite of supervisory functions are implemented across three hardware platforms. If any controller mal-function is detected, the supervisory system promptly disables the controller through a bumpless transfer method. This paper presents a detailed description of the control scheme, simulation results, the bumpless transfer method, and a redundancy and diversity method in the selection of PMU signals for feedback. This paper also describes in detail the supervisory system implemented to ensure safe and reliable damping performance of the real-time wide area damping controller.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.