Abstract

Achieving optimal data center cooling efficiency requires effective water cooling of high-heat-density components, coupled with optimal warmer water temperatures and the correct order of water preheating from any air-cooled components. The Summit and Sierra supercomputers implemented efficient cooling by using high-performance cold plates to directly water-cool all central processing units (CPUs) and graphics processing units (GPUs) processors with warm inlet water. Cost performance was maximized by directly air-cooling the 10% to 15% of the compute drawer heat load generated by the lowest heat density components. For the Summit system, a rear-door heat exchanger allowed zero net heat load to air; the overall system efficiency was optimized by using the preheated water from the heat exchanger as an input to cool the higher power CPUs and GPUs.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.