Abstract
The emissions of volatile sulfur-containing compounds from 13 flue gas desulfurization (FGD) sludge field storage sites have been characterized. Sulfur gas emissions from the sludge surfaces were determined by measuring the sulfur gas enhancement of sulfur-free sweep air passing through a dynamic emission flux chamber placed over selected sampling sites. Samples of the enclosure sweep air were cryogenically concentrated in surface-deactivated Pyrex “U” traps. Analyses were conducted by wall-coated, open-tubular, capillary column, cyrogenic gas chromatography using a sulfur-selective, flame photometric detector. Several major variables associated with FGD sludge production processes were examined in relation to the measured range and variations in sulfur fluxes including: (a) the sulfur dioxide scrubbing reagent used, (b) sludge sulfite oxidation, (c) “unfixed” or “fixed” FGD sludge, and (d) ponding or landfill storage. The composition and concentration of the measured sulfur gas emissions were found to va...
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.